IO-Link Master with IO-Link and EtherNet fieldbus interface, 4 class A and B input and output ports and IP65, IP66, IP67, IP69K rating.
Effective March 30th, 2026, ifm effector has added an 8% surcharge to this product. The surcharge will appear as a separate line item on the order.
- By ifm efector
Overview
Features
- Operating voltage:
- Standard: 20 to 30VDC
- IP69K model: 20 to 28VDC
- 300 to 3900mA current consumption
- IO-Link Master Interface:
- IO-Link revision 1.1
- COM1 (4,8 kBaud); COM2 (38,4 kBaud); COM3 (230,4 kBaud)
- Fieldbus interfaces:
- PROFINET
- PROFINET; OPC UA
- EtherNet/IP
- EtherNet/IP; OPC UA
- EtherCAT
- 4 configurable IO-Link class B ports
- Optional 4 configurable IO-Link class A ports
- Short-circuit protected inputs and outputs
- Electrical connections:
- Ethernet: D-coded M12 connectors with 4 contacts
- IO-Link: A-coded M12 connectors with 5 contacts
- Voltage supply: L-coded M12 connectors with 5 contacts
- IP65, IP66, IP67 protection rating
- IP69K with hygienic models
This product is an accessory for the following products:
Description
The ifm efector PerformanceLine IO-Link Master controls high-amperage solenoids and other devices. It supports up to eight IO-Link devices, including sensors, valves, and binary input/output modules. The DataLine series IO-Link master features an integrated fieldbus interface with daisy-chain function and IO-Link and Ethernet communication interfaces. All models feature four Class B IO-Link ports, and select models include four Class A ports. This IO-Link master features configurable current limitation for each port to ensure safe operation and allow connection to actuators up to 2A.
The PerformanceLine IO-Link master uses IO-Link and Ethernet communication interfaces to reliably transmit machine data, process parameters, and diagnostic data to the controller. All models include IO-Link connectivity and a PROFINET, EtherNet/IP, or EtherCAT fieldbus interface.
The PerformanceLine IO-Link Master offers excellent electromagnetic stability, a wide temperature range, a high protection rating, and a robust housing, making it suitable for harsh industrial environments and the food industry. All models feature A-coded M12 IO-Link connectors, D-coded M12 Ethernet connectors, and L-coded voltage connectors. Industrial models include FKM sealing on the Ethernet, IO-Link, and voltage OUT connections; meanwhile, the hygienic model has EPDM seals on these connections.
The IP69K PerformanceLine masters feature 316 stainless steel hardware to withstand the harsh environment. The housing of these hygienic models is convex, providing better cleaning angles and mounting offsets. This prevents particles and bacteria from becoming trapped during cleaning processes.
Documents
Spec Sheets
- ifm efector AL1400 PerformanceLine IO-Link Master Datasheet and Manual PDF (2.1 MB)
- ifm efector AL1401 PerformanceLine IO-Link Master Datasheet and Manual PDF (2.1 MB)
- ifm efector AL1402 PerformanceLine IO-Link Master Datasheet and Manual PDF (2.3 MB)
- ifm efector AL1403 PerformanceLine IO-Link Master Datasheet and Manual PDF (2.3 MB)
- ifm efector AL1406 PerformanceLine IO-Link Master Datasheet and Manual PDF (838 KB)
- ifm efector AL1407 PerformanceLine IO-Link Master Datasheet and Manual PDF (838 KB)
- ifm efector AL1420 PerformanceLine IO-Link Master Datasheet and Manual PDF (2.4 MB)
- ifm efector AL1421 PerformanceLine IO-Link Master Datasheet and Manual PDF (2.4 MB)
- ifm efector AL1422 PerformanceLine IO-Link Master Datasheet and Manual PDF (2.7 MB)
- ifm efector AL1423 PerformanceLine IO-Link Master Datasheet and Manual PDF (2.7 MB)
- ifm efector AL1426 PerformanceLine IO-Link Master Datasheet and Manual PDF (3.6 MB)
- ifm efector AL1427 PerformanceLine IO-Link Master Datasheet and Manual PDF (3.6 MB)
- ifm efector AL1430 PerformanceLine IO-Link Master Datasheet and Manual PDF (2.4 MB)
- ifm efector AL1431 PerformanceLine IO-Link Master Datasheet and Manual PDF (2.4 MB)
- ifm efector AL1432 PerformanceLine IO-Link Master Datasheet and Manual PDF (2.6 MB)
- ifm efector AL1433 PerformanceLine IO-Link Master Datasheet and Manual PDF (2.6 MB)
Links
Need Help? Call a Flow engineer at 1-800-884-4967
We're open 8:00 am to 5:30 pm ET