Overview

Features

  • 1 to 15 ft/sec flow range
  • Cold service: -4 to 140°F
  • Hot service: 40 to 260°F
  • ±2% accuracy
  • ±0.5% repeatability
  • Modbus RTU or BACnet MSTP
  • Scaled pulse output

Description

The Badger Meter Series 380 BTU Systems provide a low cost system for metering cold or hot systems. The 380CS/HS can accurately measure flow and temperature differential to compute energy. Utilizing either BACnet or Modbus RS-485 communications protocols or a scaled pulse output, the BTU Meter can interface with many existing control systems.

The rugged design incorporates an impeller flow sensor and two temperature probes. One temperature probe is conveniently mounted directly in the flow sensor tee. The second temperature probe is placed on either the supply or the return line depending on ease of installation for the application. These minimal connections help simplify installation and save time.

The main advantage of the Series 380 BTU meters is the cost savings over other systems offered on the market today. The integration of flow and temperature sensors provide a single solution for metering. With this system it will be possible to meter energy where it hasn't been cost effective before.

Commissioning of this meter can be completed in the field via a computer connection. Setup includes energy measurement units, measurement method, communication protocol, pulse output control, fluid density, and specific heat parameters.

RS-485 Configuration. All Series 380 BTU meters are equipped with BACnet and Modbus protocols as a standard feature. The protocol of choice can be selected and set up in the field at the users discretion. These common protocols allow for quick and easy commissioning while gaining valuable application data beyond energy total. Information such as Flow Rate, Flow Total, Energy Rate, Energy Total, Temp 1, Temp 2, and Delta T can all be transmitted on the RS-485 connection.

Scaled Pulse Output. If the RS-485 is not required for the application, a simple scaled pulse output is available. This output would represent energy total and can be set in various units of measure. This output is an open drain scaled pulse output that is compatible with a variety of PLCs, counters and also the Badger Meter 350 wireless system. This ensures the unit is easily compatible with most inputs.