TSI Alnor EBT721 Balometer
Multi-purpose electronic air balancing instrument for reading air volume flow at diffusers and grilles
Features
- Part number EBT721
- Manufactured by TSI Alnor
- Velocity
- Pitot Probe & Air Flow Probe: 25 to 15,500 ft/min
- Velocity Matrix: 25 to 5,000 ft/min
- Accuracy: up to ±3% of reading ±7 ft/min
- Pressure
- Differential Pressure: ±15 in. H2O
- Absolute Pressure: 15 to 40 in. Hg
- Accuracy: up to ±2% of reading
- Volume
- Range: 25 to 2,500 ft3/min capture hood
- Accuracy: up to ±3% of reading ±7 ft3/min
- Relative Humidity
- Range: 0 to 95% RH
- Accuracy: ±3% RH
- Temperature
- Sensor in Base: 40 to 140°F
- Temperature Probe: -40 to 250°F
- Temperature/RH Probe: 14 to 140°F
- Accuracy: up to ±0.5°F (±0.3°C)
Includes FREE
The TSI Alnor EBT721 balometer is a multi-purpose electronic air balancing instrument for reading air volume flow at diffusers and grilles. It is ideally suited for commissioning agents, test and balance contractors, facilities managers, health and safety specialists and ventilation installers. The TSI Alnor EBT721 is a lightweight, ergonomically designed kit that saves time and money, while helping to create a healthy and energy efficient environment.
Designed for use with pitot, air flow, temperature, velocity matrix or relative humidity probes, the TSI Alnor EBT721 balometer also features a detachable digital manometer that can be used for other applications. Other features of the TSI Alnor EBT721 balometer include min, max and average for up to 1,000 readings, time and date stamped data storage (1,000 readings), a user-selectable logging interval and a response time of 2 to 8 seconds.
The 6-digit, multi-line display of the TSI Alnor EBT721 balometer also features large characters (19 mm) and symbolic icons which are displayed on a high-contrast backlit LCD. A ¼ inch (6.35 mm) straight port pressure connection is also included with the EBT721 and is designed for use with 3/16 inch (4.76 mm) ID flexible tubing.
The TSI Alnor EBT721 balometer ships complete with:
- 2' x 2' air capture hood, frame and base
- Manometer
- Wheeled luggage-style carrying case
- 18" pitot probe
- 2 static pressure probes
- Two 8' Norprene tubing
- LogDat1 downloading software
- Serial interface cable
- Neck strap
- Four AA rechargeable NiMH batteries
- Internal charger
- NIST calibration
- Manual
Documents
Specifications
| Temperature Range | Sensor in Base (40 to 140°F (4.4 to 60°C))
Temperature probe (-40 to 250°F (-40 to 121°C)) Temperature/RH probe (14 to 140°F (-10 to 60°C)) |
|---|---|
| Temperature Resolution | 0.1°F (0.1°C) |
| Velocity Range | Pitot probes 25 to 15,500 ft/min (0.125 to 78 m/s)
Air flow probe 25 to 15,500 ft/min (0.125 to 78 m/s) Velocity matrix 25 to 5,000 ft/min (0.125 to 25 m/s) |
| Temperature Accuracy | ±0.5°F (±0.3°C) from 32 to 160°F (0 to 71°C) |
| Operating Temp | 40 to 140°F (4.4 to 60°C) |
| Power Supply | Four AA-size cells or AC adapter |
| Battery Life | N/A |
| Velocity Resolution | 1 ft/min (0.01 m/s) |
| Velocity Accuracy | ±3% of reading ±7 ft/min (±0.04 m/s) at
velocities >50 ft/min (>0.25 m/s) |
| Additional Information | Statistics (min, max, average up to 1000 readings) |
| Pressure Range | Differential pressure
±15 in. H2O (±3735 Pa); 150 in. H2O (37.5 kPa), maximum safe operating pressure Absolute pressure 15 to 40 in. Hg (356 to 1016 mm Hg) |
| Pressure Accuracy | ±2% of reading ±0.001 in. H2O (±0.25 Pa)
static and differential; ±2% of reading absolute |
| Output | N/A |
| Time Constant | N/A |
| Relative Humidity Range | 0 to 95% RH temperature/RH probe |
| Relative Humidity Accuracy | ±3% RH |
| Relative Humidity Resolution | 0.1% RH |
| Volumetric Flow Range | 25 to 2,500 ft3/min (42 to 4250 m3/h) capture hood |
| Volumetric Flow Accuracy | ±3% of reading ±7 ft3/min (±12 m3/h) at
flows >50 ft3/min (>85 m3/h) |
| Volumetric Flow Resolution | 1 ft3/min (1 m3/h) |